Capacitor switching switch
Category:
KS/FK capacitor switching switch selects thyristor switch and magnetic holding switch for parallel operation, which has the advantage of SCR zero crossing switching at the moment of connection and disconnection, and has the advantage of zero power consumption of magnetic holding switch during normal connection.
key word:
Hotline:
Detailed introduction
Graphic details
KS/FK capacitor switching switch is to parallelize the high voltage withstand and high current thyristor with the contact of magnetic holding relay, and automatically find the best switching point and the best switching point through microcomputer control, so as to achieve zero crossing voltage switching on and current switching off. The switching is completed by the thyristor at the moment of switching on and off, and the running current is completed by the magnetic holding relay triggered by pulse voltage to make the contact close.
KS/FK capacitor switching switch selects thyristor switch and magnetic holding switch for parallel operation, which has the advantage of SCR zero crossing switching at the moment of connection and disconnection, and has the advantage of zero power consumption of magnetic holding switch during normal connection.
KS/FK capacitor switching switch has the advantages of non impact, low power consumption, long life, etc. It can replace contactor or thyristor switch and is widely used in low-voltage reactive power compensation field.

● Rated voltage, working power supply and rated current Rated working voltage: 380V (total compensation)/220V (sub compensation) three-phase four wire AC
●50HZ; Allowable deviation: synchronous change of three-phase voltage is not more than+20%; The waveform is sine wave with distortion less than 5%; Rated frequency: 50Hz+5%;
● Rated current: 30/38/45/63/80A;
● Service life: 500000 times
● Number of phases: three-phase (△ type connection); Single phase (Y-type connection);
● Control capacity: three-phase common compensation capacitor bank capacity: 16/20/25/30/40Kvar; Total capacity of sub compensation three-phase capacitor bank: 16/20/25/30/40Kvar;
● Response time ≤ 60ms
● The altitude shall not exceed 2000 meters (if it is more than 2000 meters, it shall be corrected according to the standard)
● Ambient temperature: - 40~+50 ° C
● The installation site shall be free of violent mechanical vibration, harmful gas and steam, conductive and explosive dust
● The continuous operating voltage is 1.0Un, and the maximum long-term overvoltage does not exceed 1.1Un
● Steady state overcurrent (including harmonic current) shall not exceed 1.5In

|
Model |
Rated current/A |
Controllable capacitor capacity/kvar
|
Size |
|
380/400V |
|||
| KS/FK-45△ | 45 | 20 |
Shape: 186X1164 Installation: 171X101.3
|
| KS/FK-55△ | 55 | 30 | |
| KS/FK-70△ | 70 | 40 | |
| KS/FK-80△ | 80 | 50 | |
| KS/FK-45Y | 45 | 20 | |
| KS/FK-55Y | 55 | 30 |