KYN28A-24 armored removable AC metal enclosed switchgear
Category:
KYN28A-24 armored removable AC metal enclosed switchgear is applicable to indoor three-phase 50/60 Hz power system with rated voltage of 24 kV, mainly used in power plants and substations In industrial and mining enterprises and high-rise buildings, it receives and distributes electric energy and controls, protects and monitors circuits. KYN28A-24 switchgear equipment has various functions to prevent misoperation, including preventing the mobile handcart with negative charge, preventing the short circuit at the closed position of the grounding switch, and preventing the electrification of the grounding switch.
key word:
Hotline:
Detailed introduction
Graphic details
KYN28A-24 armored removable AC metal enclosed switchgear is applicable to indoor three-phase 50/60Hz power system with rated voltage of 24kV, mainly used in power plants and substations In industrial and mining enterprises and high-rise buildings, it receives and distributes electric energy and controls, protects and monitors circuits. KYN28A-24 switchgear equipment has various functions to prevent misoperation, including preventing the mobile handcart with negative charge, preventing the short circuit at the closed position of the grounding switch, and preventing the electrification of the grounding switch.
KYN28A-24 switchgear is equipped with advanced and reliable control and protection components. The bus adopts heat shrinkable insulation materials or epoxy coated insulation methods to optimize the electrode shape. The cabinet is compact in structure. YN28A-24 switchgear room is a distribution equipment with advanced technology, stable performance, reasonable structure, convenient application, safety and reliability.

·Ambient temperature: maximum temperature:+40 ° C, minimum temperature: - 15 ° C, and the average temperature measured within 24h shall not exceed 35 ° C.
·The temperature conditions are as follows: the average value of daily relative humidity does not exceed 95%
The average monthly relative humidity shall not exceed 90%
The average daily steam pressure shall not exceed 2.2kpa, and the average monthly steam pressure shall not exceed 8kpa
·Condensation occasionally occurs under such conditions.
·Altitude not exceeding 1000m

| name |
Company |
parameter |
|
Rated voltage |
kV | 24 |
|
Rated frequency |
Hz |
65 (interphase, to ground)/79 isolating fracture) |
|
Rated current |
A |
125 (interphase, to ground)/145 (isolating fracture) |
|
Rated short-circuit breaking current |
kA | 50 |
|
Rated short-circuit making current |
kV | 1250 |
|
4s rated short-time withstand current effective value) |
kV | 25 |
|
Rated dynamic stability current (peak value) |
kV | 63 |
|
1 min power frequency withstand voltage (effective value) |
kV | 25 |
|
Rich impulse withstand voltage (peak value) |
kV | 63 |
|
Rated operating sequence |
Hz |
Opening - 0.3 min - closing opening - 0.3 min - closing opening |
|
Degree of protection |
IP4X (housing): IP2X (circuit breaker door] open) |
Users shall provide the following information when ordering products:
·Full model of the product (including main circuit scheme number and auxiliary circuit scheme number);
·Combination sequence diagram of main circuit system;
·Electrical schematic diagram of auxiliary circuit;
·List of components in the cabinet;
·Other special requirements of the product shall be mentioned separately.
Related products
Online
Message
If you have any suggestions or feedback on our company, please fill in the relevant information on this page and submit it. A staff member will contact you in time, or please call us directly.